YuenNan Coking Factory, Blast Furnace Gas, Only 2.4Pa
1. Technical data and basic information
   ID*WD: 350*5mm        
   Medium :Blast Furnace gas
   Design temperature / pressure:  28℃ / 86kPa(A)
   WorkingProcess density: 1.0269kg/m3
  Scale/max/nor/min Flow: 3000/1000/451/ 400 Nm3/h  
   Primary element: T26 probe bar, only 100mm insert for 350mm pipe
   K-Number:  0.71239, auto compute by software 
   Coefficient of expansion: 1.0

2.  Introduce about application 
  a.  Original DP is mico-DP, produced from Oversea. NO any display about flow and Dp, always both are zero for dp      and flow.  Never normal works after mount. 
  b.  One 3 in ONE type B mounted on 3rd Sept. 2021 in site.  Due to the medium is gas and it is dangerous, and       most engineers think it is impossible to measure the very small flow.   Many departments, technics & instrument &    safety, come site to see the process. 
  c. Only take about half hour, tanking the old transmitter out, and mount MMF on the 3-valves manifold. After       open high/low valves, MMF displays only 2.4Pa and 450Nm3/h. At the time, flow velocity is only 1.65m/s. It is real   super- small DP measurement. Let everyone deeply impressed. The process can be seen follow pictures and live  video.